JE Dunn is currently working on the inital, second, and third substation for a client’s second hyperscale data center campus in the Kansas City Metro.
The first substation included coordination with utility for buildout of onsite switchyard serving substation. Worked with design team and client to help coordinate easements and utility installation. Two 345kV circuits feeding group operated air break (GOAB) switch mounted on A-frame dead-end structures. 2000A 345kV high voltage circuit breakers feeding owner furnished 120MVA, 345/13.8kV Hitachi transformers. Overhead distribution to (12) individually mounted 3000A, 15kV medium voltage circuit breakers connected to an outdoor control enclosure with SEL Relays.
The second one includes two 345kV circuits feeding group operated air break (GOAB) switch mounted on A-frame dead-end structures. 2000A 345kV high voltage circuit breakers feeding owner furnished 143MVA, 345/13.8kV Pennsylvania Transformer Technology transformers. Overhead distribution to (10) individually mounted 3000A, 15kV medium voltage circuit breakers connected to an outdoor control enclosure with SEL Relays.
JE Dunn is currently in the preconstruction phase for the third substation on campus. This build also includes Two 345kV circuits feeding group operated air break (GOAB) switch mounted on A-frame flying tap structures. 2000A 345kV high voltage circuit breakers feeding owner furnished 345/13.8kV Hyundai transformers. Overhead distribution to (12) individually mounted 3000A, 15kV medium voltage circuit breakers connected to an outdoor control enclosure with SEL Relays.